Installation Notes and Warranty Service
Installation Notes
1.
Verify the part number and description correct according to the
packing list and product labels.
2.
Apply
power to the transducers only after a through check of the input
signal, power source, and connection diagram.
3.
The Power Source voltage must be within ±2% with noise less than
0.4%. Vpp
4.
The transducers with current output may only be used with load
resistance of less than 250
Ω.
The voltage output transducers must be connected to a load of
greater that 2K
Ω
5.
The transducers should only be used in
environments having no static electricity, excessive dust, corrosive
or explosive gases.
6.
Ensure the terminal screws are tightened securely. An electrical
test with a multimeter directly at the screw terminal will ensue a
reliable installation
7.
Calibration of the units with equipment that has accuracy ratings
greater than the rating of the transducers. Ensure that the
equipment and transducers have been operating for a minimum of 15
minutes before calibration.
8.
The transducers should not be used in environments with strong
electromagnetic interference. Standard precautions such as
shielding the input and/or output lines should be observed. All
lines should be kept as short as possible. If several transducers
are used together, keep a minimum of 10 mm space between each unit.
A 35mm (width) track is to be used for DIN rail mounting withф3
screw for surface mounting.
9.
The transducers have been calibrated at the factory. Contact the
factory if field adjustments are required.
10.
Do not remove or destroy the product
labels.
|