Open Loop Hall Effect Current Sensors/Transducers
|
|
|
1. Measuring Principle
• Primary
current Ip applied on core, causing Hall voltage rise thanks
to the magnetic induction generated on core.
• Ic is a constant current source to supply Hall sensor. It
makes Hall sensor under constant operation condition.
• Output voltage Vo then is proportional to Ip. This means
that the output can get a very good linearity before core
and OP saturation. |
 |
2. Characteristics and
Features
Measurable Current Range:
About 3
times of rated current
Output Signal:
It is directly proportional to the measured current, both DC and AC
measurable. General voltage output Vo
is 4V at the rated (nominal) current Irated.
Different Vo
versions are also available
Measurement Accuracy:
Depends
on ambient temperature, operating temperature and some other
electrical parameters. Our current sensors are factorycalibrated (offset
and gain voltage) at an ambient temperature of 25°C
3. Dynamic Properties
a. Response time
• Definition:
The delay time between 90% of measurable current range (3 times of
rated current) and sensor
output reaches the coordinated voltage
• specification:
Chenyang open loop current sensors have the Best performance thanks
to our best design of layout and well selection of high slew Rate
amplifier.

b. Noise
response
• Voltage pulse applied 300~600V/μs on primary conductor
• With control power supply
• Measuring output voltage (Vo), specification depends on the
application situation. However the
smaller, the better
• Chenyang open loop current sensors have the excellent low output
voltage (Vo) in comparison with
other sensors.

c.
Output voltage (Vo) linearity:
• The output voltage versus input current relation of an ideal
current sensor (without setting error in
residual and output voltage) is indicated by the dot line in right
figure
• The continuous line shows the output/input relation of an actual
sensors.

4.
Output Voltage (Vo) Performance (at Rated Current 50A)
• Offset
standard specification:40mV
• Output voltage(Vo) standard specification: ±4V
±0.04V

5.
Typical Applications
• General
Purpose Inverter
• AC/DC Variable Speed Drivers
• Battery Supplied Applications
• Uninterruptible Power Supplies
• Switched Mode Power Supplies

Have a question? Click Here for Assistance
|