Open Loop Hall Effect Current Sensor CYHCT-E4D
This Hall Effect current sensor
is based on open loop principle and can be used for
measurement of DC currents. The output of the transducer
reflects the real wave of the
current carrying conductor.
|

|
|
Product Characteristics |
Applications |
|
• |
Excellent accuracy |
• |
Frequency conversion timing equipments |
|
• |
Very good linearity |
• |
Various power supply |
|
• |
Small size |
• |
Uninterruptible power supplies (UPS) |
|
• |
Light in weight |
• |
Electric welding machines |
|
• |
Less power consumption |
• |
Transformer substation |
|
• |
Window structure |
• |
Numerical controlled machine tools |
|
• |
Electrically isolating the output of the transducer from the
current carrying conductor |
• • |
Electrolyzing and electroplating equipments Electric powered
locomotive |
|
• |
No insertion loss |
• |
Microcomputer monitoring |
|
• |
Current overload capability |
• |
Electric power network monitoring |
|
Part number ELECTRICAL DATA |
Measuring range |
Linearity range |
Overload capacity |
|
CYHCT-E4D-10mA-XY |
10mA |
15mA |
200mA |
|
CYHCT-E4D-100mA-XY |
100mA |
150mA |
2A |
|
CYHCT-E4D-200mA-XY |
200mA |
300mA |
4A |
|
CYHCT-E4D-500mA-XY |
500mA |
750mA |
10A |
|
CYHCT-E4D-1A-XY |
1A |
1.5A |
20A |
|
CYHCT-E4D-2A-XY |
2A |
3A |
40A |
|
CYHCT-E4D-5A-XY |
5A |
7.5A |
100A |
|
CYHCT-E4D-10A-XY |
10A |
15A |
200A |
|
Supply voltage Nominal output current |
X=3 for +12V, |
X=4 for +15V, X=5 for +24V |
V mA |
|
Current consumption |
|
≤25 |
mA |
|
Galvanic isolation |
3KV RMS/50Hz/min Y=3 for 0-20mA, Y=4 for 4-20mA |
KV |
|
ACCURACY DYNAMIC PERFORMANCE |
|
Zero offset voltage |
±20 |
mV |
|
Hysteresis error |
±10 |
mV |
|
Thermal drift of offset current |
≤250 |
ppm/°C |
|
Response time |
≤10 |
μs |
|
Accuracy |
±1.0 |
% |
|
Linearity |
≤1.0 |
%FS |
|
GENERAL DATA |
|
Operating temperature |
-10 ~ +80 |
°C |
|
Storage temperature |
-25 ~ +85 |
°C |

CONNECTION
The current carrying cable must pass through the window. The phase
of output is the same as that of the current passing the window in
the direction of the arrow indicated on the case.
|
|
Wiring of Terminals: 1. +15V, +12V, +24V
|
|
2. NC
|
|
3. +Output
4. Ground |
|
 |
Notes:
1. Connect the terminals of power source, outputs respectively and
correctly, never make wrong connection.
2. Two
potentiometers can be adjusted, only if necessary, by turning slowly
to the required accuracy with a small screwdriver.
3. The best accuracy can be achieved when the window is fully filled
with bus-bar (current carrying conductor).
4. The in-phase output can be obtained when the direction of current
of current carrying conductor is the same as the direction of arrow
marked on the transducer case.
Have question?