Permanent Magnets & Hall Effect Sensors     My Account    |   Track Your Order   |   My Cart    |   F.A.Q.         
    Project Engineering     |     Collaboration Forum     |     Contact Us     |     About Us    |     Site Map       sales@bbautomacao.com


Permanent
Magnets
NdFeb Magnets
Alnico Magnets
SmCo Magnets
H. Ferrite Magnets
Rare Earth Magnets
Bonded NdFeB

Magnet Grades


Project Magnets
Custom Magnets
Industrial Magnets
Motor Magnets
Generator Magnets
Dipole Magnets
Chinese Magnets
Strong Magnets

Neodymium Magnets

Custom Neodymium
Neodymium Rings
Neodymium Bars
Neodymium Blocks
Neodymium Cylinders
Neodymium Discs
Neodymium Spheres
Coated Neodymium

Hall Effect Sensors

Vane Sensors
ICs/Elements
Gear Tooth Sensors
Current Sensors
Voltage Sensors
Analog Sensors
Digital Sensors

Measuring Devices
Gauss/Tesla Meters
Magnetic Fluxmeters
Magnetic Field Viewer


Checkout


Search
Terms & Policies
Magnet manufacturers
Neodymium China

 

 

 
 


Open Loop Hall Effect Current Sensor CYHCT-E4C

This Hall Effect current sensor is based on open loop principle and can be used for
measurement of DC currents. The output of the transducer reflects the real wave of the
current carrying conductor.
 



Product Characteristics

Applications

•

Excellent accuracy

•

Frequency conversion timing equipments

•

Very good linearity

•

Various power supply

•

Small size

•

Uninterruptible power supplies (UPS)

•

Light in weight

•

Electric welding machines

•

Less power consumption

•

Transformer substation

•

Window structure

•

Numerical controlled machine tools

•

Electrically isolating the output of the transducer from the current carrying conductor

• •

Electrolyzing and electroplating equipments Electric powered locomotive

•

No insertion loss

•

Microcomputer monitoring

•

Current overload capability

•

Electric power network monitoring

 

Part number ELECTRICAL DATA

 

Measuring range

 

Linearity range

 

Overload capacity

CYHCT-E4C-10mA-XY

10mA

15mA

200mA

CYHCT-E4C-100mA-XY

100mA

150mA

2A

CYHCT-E4C-200mA-XY

200mA

300mA

4A

CYHCT-E4C-500mA-XY

500mA

750mA

10A

CYHCT-E4C-1A-XY

1A

1.5A

20A

CYHCT-E4C-2A-XY

2A

3A

40A

CYHCT-E4C-5A-XY

5A

7.5A

100A

CYHCT-E4C-10A-XY

10A

15A

200A

Supply voltage Nominal output current

X=1 for ą12Vą5%,

X=2 for ą15Vą5%

V mA

Current consumption

≤25 Y=3 for 0-20mA, Y=4 for 4-20mA

mA

Galvanic isolation

3KV RMS/50Hz/min

KV

ACCURACY DYNAMIC PERFORMANCE

Zero offset voltage

ą20

mV

Hysteresis error

ą10

mV

Thermal drift of offset current

≤250

ppm/°C

Response time

≤10

μs

Accuracy

ą1.0

%

Linearity

≤1.0

%FS

GENERAL DATA

Operating temperature

-10 ~ +80

°C

Storage temperature

-25 ~ +85

°C

CONNECTION
The current carrying cable must pass through the window. The phase of output is the same as that of the current passing the window in the direction of the arrow indicated on the case.



Wiring of Terminals: +: +15V/+12V Power Supply

-:

-15V/-12V Power Supply

M:

Output

G:

Ground

Notes:

1. Connect the terminals of power source, outputs respectively and correctly, never make wrong connection.

2. Two potentiometers can be adjusted, only if necessary, by turning slowly to the required accuracy with a small screwdriver.

3. The best accuracy can be achieved when the window is fully filled with bus-bar (current carrying conductor).

4. The in-phase output can be obtained when the direction of current of current carrying conductor is the same as the direction of arrow marked on the transducer case.

 

Have  question? Please Click Here for Support

power_transducer_close_loop_threshold
Engineering Forum

 

 

Home | Products | Search | Checkout | About us | Contact us | Site map

© Copyright BB Automacao Inc.

4 Cedar Swamp Rd.
Glen Cove, New York 11
542
nyc@bbautomacao.com
Ph.: 516-277-1278
Fax: 516-776-9353