This Hall Effect current sensor
is based on open loop principle and can be used for
measurement of AC and DC currents. The output (rms) of the
transducer reflects the real
wave of the current carrying conductor.
Product Characteristics
Applications
Excellent accuracy
Frequency conversion timing equipments
Very good linearity
Various power supply
Split Cores
Uninterruptible power supplies (UPS)
Light in weight
Current measuring instruments
Less power consumption
Transformer substation
Window structure
Numerical controlled machine tools
Electrically isolating the output of the transducer from the
current carrying conductor
Electrolyzing and electroplating equipments Electric powered
locomotive
No insertion loss
Microcomputer monitoring
High current overload capability
Electric power network monitoring
Part number ELECTRICAL DATA
Measuring range
Linearity range
Overload capacity
CYHCS-E6H-300A-XY
300A
450A
6kA
CYHCS-E6H-400A-XY
400A
600A
8kA
CYHCS-E6H-500A-XY
500A
750A
10kA
CYHCS-E6H-600A-XY
600A
900A
12kA
CYHCS-E6H-800A-XY
800A
1200A
16kA
CYHCS-E6H-1000A-XY
1000A
1500A
20kA
Supply voltage Nominal output voltage (tracing voltage
output)
X=1 for ą12Vą5%, X=2 for ą15Vą5% Y=1 for ą4V, Y=2 for ą5V
Current consumption
≤25mA
Galvanic isolation
3KV RMS/50Hz/min
ACCURACY DYNAMIC PERFORMANCE
Zero offset voltage
ą20
mV
Hysteresis error
ą10
mV
Thermal drift of offset current
≤250
ppm/°C
Response time
≤10
μs
Accuracy
ą1.0
%
Linearity
≤1.0
%FS
GENERAL
DATA
Operating temperature
-10 ~ +80
°C
Storage temperature
-25 ~ +85
°C
DIMENSIONS
(mm)
CONNECTION
The current carrying cable must pass through the window. The phase
of output is the same as that of the current passing the window in
the direction of the arrow indicated on the case.