1. General Specifications |
| Linearity Range |
1.5 times of the maximum measuring range |
Response Time |
10µs |
| Overload Capability |
2.0 times of the maximum measuring range |
Current Consumption |
25mA+Output Current |
| Accuracy |
0.5% |
Isolation |
3KV RMS/50Hz/min |
| Offset Voltage |
0.2mV |
Operating Temperature |
-10°C ~ +80°C |
| Hysteresis Error |
0.2mV |
Storage Temperature |
-25°C ~ +85°C |
| Temperature Drift |
200ppm/°C |
Fire Retardancy |
UL94-V0 |
|
|
2. Input/Output Range and Case Types |
| Part Number |
Output Range |
Power Supply |
Window Dimension (mm) |
Case Type |
Measuring Range |
| CY-IZ04-D |
0 ~ 200mA |
±12V ±15V |
Ø20 |
D2 |
0-400A |
| 0 ~ 150mA |
Ø20.5 |
D6 |
0-300A |
| 0 ~ 100mA |
Ø 36 |
D7 |
0-500A |
|
|
3. Product Characteristics |
| Small size, light in weight, less power consumption, window structure, electrically isolating
the output of the transducer from the current carrying conductor, no insertion loss.
|
|
|
4. Applications |
|
These sensors can be used for measuring DC, AC and pulsed currents, for Frequency conversion timing equipment,
various power supply, UPS, electric welding machine, transformer substation, numerical control machine tool,
electrolyzing equipment, electroplating equipment, electric powered locomotive, microcomputer monitoring, electric
power net monitoring. |
|
|
|