There are two kinds of Intelligent Electric Isolation Transducers. One is for single-phase Circuits/systems and another
is for three-phase circuits/systems. The three-phase type has two connections: 3-wires and 4-wires.
|
| Input: |
Voltage, current |
| Output parameter: |
Voltage, current, active and reactive power, power factor, frequency and energy |
| Interface: |
RS-485 or RS-232C |
| Power supply: |
Steady voltage power supply (the code of the type is 1~4) and wide voltage range power supply
(the code of the type is 5~9). The former is called the steady voltage input mode and the latter
is called the wide voltage input mode |
| Isolation Voltage: |
1000V (wide voltage input mode) and 2500V (steady voltage input mode) |
| Accuracy: |
0.5% |
| Advantages: |
Small size, powerful function, strong isolation between voltage/current input and output.
Its ID address can be set and modified by software of monitoring system. |
|
| Circuits/Systems |
Part Number |
Interface |
Data Format |
Isolation |
Case Style |
| Single-phase connection |
CY-AJ11-1 |
RS 485 |
ASCII |
Double isolation |
S3 |
| CY-AJ11-2 |
RS 232C |
ASCII |
Double isolation |
S3 |
| 3-phase-3-wire connection (two watt meter method) |
CY-AJ31-1 |
RS 485 |
ASCII |
Double isolation |
S3, N |
| CY-AJ31-2 |
RS 232C |
ASCII |
Double isolation |
S3, N |
| CY-AJ32-1 |
RS 485 |
ASCII |
Treble isolation |
N |
| CY-AJ32-2 |
RS 232C |
ASCII |
Treble isolation |
N |
| 3-phase-4-wire connection |
CY-AJ41-1 |
RS 485 |
ASCII |
Double isolation |
S3, N |
| CY-AJ41-2 |
RS 232C |
ASCII |
Double isolation |
S3, N |
| CY-AJ42-1 |
RS 485 |
ASCII |
Treble isolation |
N |
| CY-AJ42-2 |
RS 232C |
ASCII |
Treble isolation |
N |
|
Characteristics
-
It combines collector and transmitter, and can measure voltage, current, frequency, active power,
reactive power, power factor as well as accumulative total energy simultaneously.
-
Full-digital AC sampling technology with high accuracy and stability.
-
Current, voltage input and RS-485 or RS-232C digital interface output, which can connect with computer and the network directly.
-
Output data format: ASCII format.
-
Fully-isolated processing with high anti-interfere ability
-
Multi-kinds of flexible installation method
|
|
Applications
It is applicable for electric power lines, automatic monitoring systems of equipments, industrial automatic control
systems, supervising systems of rectifying circuits of telecommunication facilities, electric railway,
intelligent residential district, intelligent buildings, automatic power supply and auto-recording
systems for business mansions, safety monitor systems. It also can be used for the key device of electronic kWh
meters and pre-pay kWh meters.
|
|
|